What size gas line for a water heater?

The gas line size for a water heater is 1/2 inch Schedule 40 pipe on runs up to 150 feet, then 3/4 inch from 175 to 200 feet. A typical residential water heater is rated 40,000 BTU per hour, which is 40 CFH of natural gas, and the required pipe grows with the length of the run because capacity falls as gas travels.

Required gas line size for a water heater at every run length

A standard 40 to 50 gallon atmospheric tank water heater. Measure the longest run from the gas meter to the appliance, round that measurement up to the next row, and read the size. Rounding down is the single most common way a line ends up undersized. Demand here is fixed at 40 CFH; only the length changes.

Longest runSmallest pipe that worksIts capacityMargin over 40 CFH
10 ft1/2 inch172 CFH132 CFH spare
20 ft1/2 inch118 CFH78 CFH spare
30 ft1/2 inch95 CFH55 CFH spare
40 ft1/2 inch81 CFH41 CFH spare
50 ft1/2 inch72 CFH32 CFH spare
60 ft1/2 inch65 CFH25 CFH spare
70 ft1/2 inch60 CFH20 CFH spare
80 ft1/2 inch56 CFH16 CFH spare
90 ft1/2 inch52 CFH12 CFH spare
100 ft1/2 inch50 CFH10 CFH spare
125 ft1/2 inch44 CFH4 CFH spare
150 ft1/2 inch40 CFH0 CFH spare
175 ft3/4 inch77 CFH37 CFH spare
200 ft3/4 inch71 CFH31 CFH spare

Where the size steps up

The answer is not one size. It is 1/2 inch through 150 feet, then 3/4 inch through 200 feet. Each step happens at the first column where the smaller pipe can no longer carry 40 CFH within the code allowance of 0.5 inches water column. Anyone quoting a single size for a water heater without asking how far the run is has skipped the half of the calculation that actually varies.

Worked examples at the four most common runs

Each of these shows the full NFPA 54 lookup for that distance, the nearby sizes and the margin:

If a second appliance shares the run

The code sizes the total connected load, so this is where undersized lines come from. At 60 feet a water heater alone needs 1/2 inch. Add a 100,000 BTU furnace to the same pipe and the connected load becomes 140,000 BTU, or 140 CFH, which needs 1 inch at that same 60 feet — a size up from the single-appliance answer. Size the pipe for everything that will ever hang off it.

Propane instead of natural gas

Propane carries 2,516 BTU per cubic foot against natural gas at 1,000, so the same water heater draws only 16 CFH on LP. PlumbCalc returns 1/2 inch at 20 feet and 1/2 inch at 100 feet. Those figures are deliberately conservative — they are read off the natural gas table, so they come back equal to or larger than a dedicated LP table would give. Confirm any LP work against an LP table and local code.

Before you cut any pipe

These figures come straight from NFPA 54 Table 402.4(2) for Schedule 40 metallic pipe, natural gas at 0.60 specific gravity, inlet pressure under 2 psi and an allowable pressure drop of 0.5 inches water column. That is the ordinary residential case, and it is the same table the PlumbCalc gas line sizing calculator uses.

Two things change the answer on a real job. First, the code sizes the total connected load on a run, not one appliance in isolation — if a second appliance shares the pipe, add its BTU rating before you size. Second, a 2 psi system, a CSST or copper material, or a longer allowable pressure drop all use different tables entirely. Size to the longest run, size to the full load, and confirm against your local code and the appliance data plate before installing.

The governing standard is the National Fuel Gas Code, published as NFPA 54 and adopted in most of the United States — see the National Fuel Gas Code for background on the code itself.

Related sizing references

Frequently asked questions

What size gas line does a water heater need?

A typical 40,000 BTU water heater draws 40 CFH of natural gas and needs 1/2 inch up to 150 feet, 3/4 inch from 175 to 200 feet, in Schedule 40 metallic pipe. The size depends on the longest run from the meter, so measure the run before you buy pipe.

Why does the run length change the gas line size for a water heater?

Gas loses pressure to friction as it travels, and NFPA 54 Table 402.4(2) is built around a fixed allowable drop of 0.5 inches water column. A longer run spends that allowance sooner, so the same diameter delivers fewer CFH. That is why the table has a column for every length from 10 to 200 feet.

What if my water heater is rated higher than 40,000 BTU?

Use the rating on the appliance data plate, never the typical figure. Divide the real BTU input by 1,000 for natural gas to get CFH demand, then read down the column for your run length until you reach a capacity that meets it. The PlumbCalc gas line sizing calculator does exactly that in one step.

Can a water heater share a gas line with another appliance?

Yes, but you must size for the combined load. At 60 feet the water heater alone needs 1/2 inch; add a 100,000 BTU furnace and the 140 CFH total needs 1 inch. Add every BTU rating on the run together before you look at the table.

Does this cover CSST, copper or a 2 psi system?

No. These sizes are Schedule 40 metallic pipe on an ordinary under-2-psi residential system with a 0.5 inch water column drop. CSST, copper tubing and polyethylene each have their own capacity tables, CSST varies by manufacturer, and a 2 psi system with appliance regulators uses a different table entirely and usually allows smaller pipe over long runs.

Size your gas line with the free calculator

Get the sizing right before the inspector does.

The pipe and gas sizing cheat sheet we keep on the phone — the numbers, and the three that fail inspection most often.