What size gas line for a pool heater?

The gas line size for a pool heater is 3/4 inch Schedule 40 pipe on runs up to 10 feet, then 1 inch from 20 to 60 feet, then 1-1/4 inch from 70 to 200 feet. A typical residential pool heater is rated 250,000 BTU per hour, which is 250 CFH of natural gas, and the required pipe grows with the length of the run because capacity falls as gas travels.

Required gas line size for a pool heater at every run length

A residential gas pool or spa heater. This is usually the single largest load on a house. Measure the longest run from the gas meter to the appliance, round that measurement up to the next row, and read the size. Rounding down is the single most common way a line ends up undersized. Demand here is fixed at 250 CFH; only the length changes.

Longest runSmallest pipe that worksIts capacityMargin over 250 CFH
10 ft3/4 inch360 CFH110 CFH spare
20 ft1 inch466 CFH216 CFH spare
30 ft1 inch374 CFH124 CFH spare
40 ft1 inch320 CFH70 CFH spare
50 ft1 inch284 CFH34 CFH spare
60 ft1 inch257 CFH7 CFH spare
70 ft1-1/4 inch486 CFH236 CFH spare
80 ft1-1/4 inch452 CFH202 CFH spare
90 ft1-1/4 inch424 CFH174 CFH spare
100 ft1-1/4 inch400 CFH150 CFH spare
125 ft1-1/4 inch355 CFH105 CFH spare
150 ft1-1/4 inch322 CFH72 CFH spare
175 ft1-1/4 inch296 CFH46 CFH spare
200 ft1-1/4 inch275 CFH25 CFH spare

Where the size steps up

The answer is not one size. It is 3/4 inch through 10 feet, then 1 inch through 60 feet, then 1-1/4 inch through 200 feet. Each step happens at the first column where the smaller pipe can no longer carry 250 CFH within the code allowance of 0.5 inches water column. Anyone quoting a single size for a pool heater without asking how far the run is has skipped the half of the calculation that actually varies.

Worked examples at the four most common runs

Each of these shows the full NFPA 54 lookup for that distance, the nearby sizes and the margin:

If a second appliance shares the run

The code sizes the total connected load, so this is where undersized lines come from. At 60 feet a pool heater alone needs 1 inch. Add a 100,000 BTU furnace to the same pipe and the connected load becomes 350,000 BTU, or 350 CFH, which needs 1-1/4 inch at that same 60 feet — a size up from the single-appliance answer. Size the pipe for everything that will ever hang off it.

Propane instead of natural gas

Propane carries 2,516 BTU per cubic foot against natural gas at 1,000, so the same pool heater draws only 99 CFH on LP. PlumbCalc returns 1/2 inch at 20 feet and 3/4 inch at 100 feet. Those figures are deliberately conservative — they are read off the natural gas table, so they come back equal to or larger than a dedicated LP table would give. Confirm any LP work against an LP table and local code.

Before you cut any pipe

These figures come straight from NFPA 54 Table 402.4(2) for Schedule 40 metallic pipe, natural gas at 0.60 specific gravity, inlet pressure under 2 psi and an allowable pressure drop of 0.5 inches water column. That is the ordinary residential case, and it is the same table the PlumbCalc gas line sizing calculator uses.

Two things change the answer on a real job. First, the code sizes the total connected load on a run, not one appliance in isolation — if a second appliance shares the pipe, add its BTU rating before you size. Second, a 2 psi system, a CSST or copper material, or a longer allowable pressure drop all use different tables entirely. Size to the longest run, size to the full load, and confirm against your local code and the appliance data plate before installing.

The governing standard is the National Fuel Gas Code, published as NFPA 54 and adopted in most of the United States — see the National Fuel Gas Code for background on the code itself.

Related sizing references

Frequently asked questions

What size gas line does a pool heater need?

A typical 250,000 BTU pool heater draws 250 CFH of natural gas and needs 3/4 inch up to 10 feet, 1 inch from 20 to 60 feet, 1-1/4 inch from 70 to 200 feet, in Schedule 40 metallic pipe. The size depends on the longest run from the meter, so measure the run before you buy pipe.

Why does the run length change the gas line size for a pool heater?

Gas loses pressure to friction as it travels, and NFPA 54 Table 402.4(2) is built around a fixed allowable drop of 0.5 inches water column. A longer run spends that allowance sooner, so the same diameter delivers fewer CFH. That is why the table has a column for every length from 10 to 200 feet.

What if my pool heater is rated higher than 250,000 BTU?

Use the rating on the appliance data plate, never the typical figure. Divide the real BTU input by 1,000 for natural gas to get CFH demand, then read down the column for your run length until you reach a capacity that meets it. The PlumbCalc gas line sizing calculator does exactly that in one step.

Can a pool heater share a gas line with another appliance?

Yes, but you must size for the combined load. At 60 feet the pool heater alone needs 1 inch; add a 100,000 BTU furnace and the 350 CFH total needs 1-1/4 inch. Add every BTU rating on the run together before you look at the table.

Does this cover CSST, copper or a 2 psi system?

No. These sizes are Schedule 40 metallic pipe on an ordinary under-2-psi residential system with a 0.5 inch water column drop. CSST, copper tubing and polyethylene each have their own capacity tables, CSST varies by manufacturer, and a 2 psi system with appliance regulators uses a different table entirely and usually allows smaller pipe over long runs.